|
Test
Procedure
The
plugs were initially torqued to approximately 50% of the maximum
torque values obtained from a previous test for aluminum and installed
into three commercial grade aluminum manifolds that had port positions
specially located for this test. Three manifolds were designed
(6061 T6 Aluminum) with (3) ports on (3) sides and manifold #
3 had (2) ports on (2) sides. The manifolds allowed testing (3)
samples of each SAE J1926 port sizes #2, #3, #4, #5, #6, #8, #10,
and #12 on (3) manifolds. The rated working pressure of aluminum
was 3000 psi. The manifolds were then plumbed into the impulse
stand. The test setup used conventional petroleum base ISO VG
32 oil at a temperature of 100°F+/-10°F. A relief valve
was plumbed in to control the pressure required to pass the NFPA
standard T2.6.1R2-2000. The manifolds were installed so that the
fluid flowed through the setup. This method ensures the most uniform
fluid temperature and pressure waveform characteristics, as well
as efficiently bleeding out any entrained air. The test was set
up to meet the NFPA fatigue standard T2.6.1R2-2000.
The
fatigue testing parameters outlined by the NFPA standards T2.6.1R2-2000
were as follows:
Test Duration*........1,000,000 cycles
Cycle Rate............1.0Hz
Test Pressure.........3688 psi
Test Temperature......100° F ±10°F
Test Oil..............Benz Oil petroleum base ISO VG 32
* Test continued for a total of 2,000,000 cycles.
The
goal of this project at the Fluid Power Institute® was to
establish torque values that successfully pass the 1,000,000 cycles
Endurance Test specified in paragraph 8 of NFPA T2.6.1R2-2000.
To determine torque values for EPCO anodized aluminum Zero-Leak
Gold Plugs an iterative procedure was established. The plugs were
anodized and dyed gold per MIL-A-8626 TYPE II Class 2 per Fort
Wayne Anodizing.
Starting
torque values for this evaluation were 50% of the values obtained
from previous testing, test report titled “Zero Leak Gold
Plug Testing” Project number 51579 dated 2/24/99, page 6
performed by the Fluid Power Institute at the Milwaukee School
of Engineering (for torque values see Table 1).
Each
plug size torque was increased by 20% in succession until successful
completion of the NFPA 1,000,000-cycle Endurance Test.
|
Fitting
Dash number |
Starting
Torque Values (ft-lbs) |
|
-2 |
1 |
|
-3 |
2 |
|
-4 |
3 |
|
-5 |
4 |
|
-6 |
5 |
|
-8 |
14 |
|
-10 |
23 |
|
-12 |
26 |
Table
1: Starting Torque Values
For
each test, the torque value was applied to the plugs and the manifold
assemblies were plumbed into the impulse chamber and the Rated
Fatigue Pressure Endurance Cycle Test started. The Cyclic Test
Pressure (CTP) applied will be 3688 psi for Aluminum. Pressure
waveforms for the 1,000,000 cycles Endurance Test will be in accordance
with characteristics specified by paragraph 8 of T2.6.1R2-2000.
The basic criteria for the wave shape is maximum rate of pressure
rise must not exceed 80,000 psi/sec. The NFPA T2.6.1R2-2000, paragraph
8.4.4 states, “The Pulse Duration must be held to 100±10
milliseconds”.
When a failure
occurs, a new Buna nitrile 70 durometer O-Ring will be installed
on the plug size that failed and the torque will be increased
to the next value for that size plug only. The port surface area
and the plug will be cleaned to remove any fluid or residue prior
to replacing the plug in the manifold to resume the testing. This
process will be followed until all plugs pass the 1,000,000 cycles
Endurance Test. A failure defined by NFPA T2.6.1R2-2000 states
“ The inability to sustain a given load or to contain pressure
in a pressure containing envelope”. By the stated definition
a leak would cause a failure.
The final
tests conducted on the plugs will be the Proof and Burst Tests.
These tests require new aluminum Zero-Leak Gold Plugs with Buna
nitrile 70 durometer O-Rings to be installed. The Proof and Burst
Tests will be conducted in accordance with paragraphs 4.1 and
4.2 of SAE J1644 May93. Stated briefly “the Proof Pressure
Test requires (3) samples to meet or exceed a ratio of 2:1 between
proof and working pressure for 60 seconds minimum”. The
Burst Test requirement states “ (3) samples be capable of
withstanding the minimum of four times working pressure without
failing”. During the test, O-Ring Ports will be labeled
and scribed with a scratch across the Zero-Leak Gold aluminum
plug leading into the manifold. From this mark it can be determined
if any movement of the plug in relation to manifold has occurred.
Torque values will be recorded after the test to determine if
values had changed. The pressure fatigue test will then run until
the plugs began to show signs of leakage or o-ring extrusion.
If leakage or o-ring extrusion occurs on a plug, all three plugs
of that size will be removed to examine the o-rings and plugs.
If the o-ring or plug is damaged, they will be replaced. The plugs
will then be torqued to a new torque value, approximately 20%
greater then the previous value. This procedure will be repeated
until the plugs achieve the minimum torque value needed to pass
the million cycles without leaking. The impulse stand will run
24 hours a day, seven days a week for 1,000,000 cycles, except
being shut down for maintenance or part failure.
After
the fatigue testing is completed, the plugs will be torqued to
their minimum values in high-pressure fittings. In the high-pressure
fittings, the plugs will be subjected to a proof test (SAE J343
4.2 MAR 1999) and burst test (SAE J343 4.4 MAR 1999). The proof
test consists of three of each size fitting passing a 2 to 1 working
pressure of 3000 psi (6000 psi) for a duration of no less then
30 seconds nor more than 60 seconds. After passing the proof test
the three fittings of each size will be subjected to a burst test.
In the burst test the pressure will be increased at a constant
rate to obtain the minimum burst pressure within a period of not
less than 15 seconds nor more than 60 seconds. To pass the burst
test the minimum burst pressure must equal to or greater than
4 times the working pressure of 3000 psi (12000 psi).
1Test
Report titled “Zero Leak Gold Plug Testing” Project
number 51579 dated 2/24/99 page 6 performed by the Fluid Power
Institute at the Milwaukee School of Engineering.
|