|
Testing
EPCO
Zero-Leak Gold plugs were installed into (6) specially
designed manifolds. The manifolds tested were made from standard
industry Ductile Iron and Aluminum. Three manifolds were made
of each material. The (6) manifolds were designed to install (8)
different fittings allowing (3) samples of each size to be mounted.
Two manifolds were designed with (3) ports on (3) sides and manifold
# 3 had (2) ports on (2) sides. The manifolds allowed testing
(3) samples of each SAE J1926 port sizes #2, #3, #4, #5, #6, #8,
#10, and #12 on (3) manifolds in both Aluminum and Ductile Iron
(see detail drawings in Appendix A pages 18-23). The rated working
pressure of Ductile Iron is 5000 psi and 3000 psi for aluminum.
The goal of the project at MSOE was to establish torque values
that successfully pass the 1,000,000 cycle Endurance Test specified
in paragraph 8 of NFPA /T2.6.1 R1-1991.
The
SAE published values for torque were used as a bench mark for
this test. To determine torque values for EPCO Zero-Leak Gold
plugs an iteration procedure was established.
Torque
values of 25%, 40%, 60%, 70% and 90% of SAE numbers would be tested
in succession until successful completion of the NFPA 1,000,000-cycle
Endurance Test.
For
each test, the torque value was applied to the plugs and the manifold
assemblies were plumbed into the impulse chamber and the Rated
Fatigue Pressure Endurance Cycle Test was started (see Figure
1. Test Stand Schematic). The Cyclic Test Pressure (CTP) applied
was 3688 psi for Aluminum and 6156 psi for Ductile Iron (see Calculations
in Appendix A). Pressure waveforms for the 1,000,000 cycle Endurance
Test conformed to the characteristics specified by paragraph 8
of NFPA /T2.6.1 R1-1991 (see Appendix A for waveform plots). The
basic criteria for the wave shape is maximum rate of pressure
rise must not exceed 50,000 psi/sec, the values at MSOE were 49,363
psi/sec for Ductile Iron and 39,769 for Aluminum. The NFPA /T2.6.1
R1-1991, paragraph 8.4.4 states, "The Pulse Duration must
be held to 100± 10 milliseconds" and the tests at MSOE
ran at 92 milliseconds for Ductile Iron and 98 milliseconds for
Aluminum (see Appendix A page 1 and 2 for Ductile Iron and 3 &
4 for Aluminum).
Testing
was started and if a failure occurred new O-Rings would be installed
and the torque would be increased to the next value. This process
was followed until all fittings passed the 1,000,000 cycle Endurance
Test specified in paragraph 8 of NFPA /T2.6.1 R1-1991. A failure
defined by NFPA /T2.6.1 R1-1991 states " The inability to
sustain a given load or to contain pressure in a pressure containing
envelope". By the stated definition a leak would cause a
failure. The initial test was done with 0.5 ft-lbs. torque applied
to each plug. This torque was successful at sealing at static
rated pressures, however it failed early into the endurance test.
Initial
torque values were 25% of SAE values. There were (5) test torque
trials (.5ft-lbs, 25%, 40%, and 2 trials at 60%) until the final
torque values values passed the 1,000,000 cycle Endurance
Test (final values are listed in Table
1).
The
final tests conducted on the plugs were the Proof and Burst Tests.
For these tests new Zero-Leak Gold plugs and O-Rings
were installed. The Proof and Burst Tests were conducted in accordance
with paragraphs 4.1 and 4.2 of SAE J1644 May93. Stated briefly
"the roof Pressure Test requires (3) samples to meet or exceed
a ratio of 2:1 between proof and working pressure for 60 seconds
minimum". The Burst Test requirement states " (3) samples
be capable of withstanding the minimum of four times working pressure
without failing". All EPCO Zero-Leak Gold
plugs passed both the Proof and Burst Tests criteria (see
Table 2).
|